Product Specification

H. T. Transformer

Technical Specifications

Technical Particulars
Specifications
Rated KVA
63kVA - 3150kVA
Rated Primary Voltage
11 KV
Rated Secondary Voltage
433 Volts
Primary Connections
Delta
Secondary Connections
Star
Vector Group
DYN 11
Rated Frequency
50 Hz
No of Phases
Three
Installation
Out Door
Cooling
Onan
Ambient Conditions
Ref. IS-2026
Rise of Temp. in Oil., By Thermometer Above Ambient
50 Deg. C
Separate Source Voltage Withstand Test For 60 Sec
PRI 28 KV/SEC3KV
Winding Material
Copper EC Grade
Core Material Low Loss High Permeability
CRGO M4
Oil Transformer Oil Conforming TO
IS - 335
Thermal Class
A
Tolerance on Performance
As per IS 2026
Tolerance on Weights & Dimensions
+/- 10%
Schedule of Fittings
Lifting Lugs
2 nos.
Earthing Terminals
2 nos.
Oil Filling Point with Cover
01 nos.
Drain Valve Plug
01 nos.
Oil Filter Valve
01 nos.
Name Plate
01 nos.
Terminal Plate
01 nos.
Tap Switch of Load with Locking Device & Handle
01 nos.
Thermo Meter Pocket
01 nos.
Dial Type Thermometer (4" Dial)
01 nos.
Conservator With Drain Plug & Oil level Gauge
01 nos.
Air Release Device
01 nos.
Bi-Directional Rollers (Flat)
04 nos.
HV Terminals (3 NOS. Bushings) Delta Connection
03 nos.
I.V. Terminals In Box (Star Connection)
04 nos.


Core
Core is made from best grade imported cold rolled grain oriented silicon steel lamination with the latest techique of annealing. Interleaved and mitered joints reduce the core losses and magnetizing current considerably. Core is specially designed to sustain over-fluxing up to 12.5%. Core is clamped with steel channels rigidly to reduce to cartite sound level and earthed with electrical grade copper sheet.

Winding

The winding can be of any type (i) spiral (ii) Crossover (iii) helical (iv) disc, designed to withstand the optimum electrical, mechanical, dynamic and thermal stresses depending upon the current and voltage. The coils are wound with electrolytic grade high conductivity, annealed wire and strips covered with high quality insulation. All coils are reinforced, insulated to withstand the effect of short circuits and impulse voltage shocks. Cooling ducts are provided to minimize the hotspot temperature and temperature gradient between winding and oil.

Insulation and Oil

  • The insulation material like pre-compressed boards, corrugated cylinders, Bakelite tube, insulating tapes, empire sleeves, glass sleeves varnish, epoxy bushing, porcelain bushing etc. are used of best quality to ensure long life to the transformers. Oil used as a coolant and insulating medium is of the best quality conforming to IS: 335. Before filling into Filtration Plant' and tested to ensure free from moisture and dust.
  • Tank and Radiator: The tanks are made from premium quality mild steel sheets, plates and pipes by electrical welding. Proper bracing and stiffeners are provided for robust construction. The tank are tested at specific pressure for leakage at joints/welds. Sufficient cooling radiators are provided for maximum dissipation of heat during extreme ambient temperatures. The radiators are made from best grade pressed steel fins or elliptical tubes.
Painting
Tank surface exposed to atmosphere is painted with two coats of red oxide paint to provide maximum resistance to corrosion and two coats of epoxy based anti-corrosive enamel paint. Surface in contact with oil is treated with two coat of 'Oil and Heat Resistant Paint'. This paint has more effective resistance compared to ordinary enamel paint against corrosion and oil/heat reactions.

Vector Group
  • Various vector groups can be provided as per demand.
  • Temperature Rise: Our transformers are designed for maximum temperature rise at full rated load 40°C/50°C for oil/winding for aluminium wound transformers and 45°C/55°C for copper wound transformers.
Overloading
Our transformers are designed for overloading excess than normal rating as per IS: 6600.

Fitting and Accessories
Standard fitting recommended in IS 2026-1977 are provided. Extra fittings like buchholzrelay, dial type thermometer, winding temperature indicator, marshalling box, H.V. & I.V. cable boxes, PRV and OSP are provided as per the requirement of the customers.